Linearmode Dual Mode Chargers using
Regulated Charge Current,
Wall Plug-in and Desktop  Styles

Medical
and
Information Technology


Gel Cell/Lead Acid Dual Mode Battery Chargers

  • Can provide the shortest possible charging time due to faster charge replenishment at the higher charge voltage.
  • Good for applications where the battery is discharged and charged on a frequent basis.

Standard Specifications 

  • Input Voltage: 100,120,230 or 115/230 Vac 50,60 or 50/60 Hz
  • Operating Temperatures: 0-40°C
  • Output Voltage Tolerance: +/-1%
  • Designed for Continuous Duty
  • SELV Output
  • Wall Plug-In (H&F Cases Only) or Desktop Configurations
  • 3 Year Warranty

Available Features 

  • On-Off Power Switch
  • Temperature Compensated Charging Voltage
  • Expanded Operating Temperature Range
  • LED's Indicating Power On and High Charge
  • Output Cord Sets and Connector Configurations
  • Case Colors, Markings and Company Logos
  • Auxiliary Power Supply Output

Safety Compliance 

     Designed to:
                  UL 60601-1, 60950-1  
                  CSA 22.2 #601.1, #60950 
                  EN 60601.1, 60950.1 & CE

Domestic
Models
120 Vac 60Hz
Plug-In/Desktop Desktop/IEC
Case Size H F K X Y
Power Code "1" "1" "1" "2" "3" "1" "1"
Enclosure Power Rating for
12V cell voltage
4.9W 7.2W 4.9W 7.2W 11W 20W 24W
Model # Cells Float
Charge
Volts
High
Charge
Volts
Charge Current / Amps
L[bcd]06-[gh] 3 6.9V 7.35V .57 .83 .57 .83 1.3 2.3 2.8
L[bcd]08-[gh] 4 9.2V 9.8V .46 .67 .46 .67 1.0 1.9 2.2
L[bcd]10-[gh] 5 11.5V 12.25V .40 .59 .40 .59 .89 1.6 1.9
L[bcd]12-[gh] 6 13.8V 14.7V .35 .52 .35 .52 .80 1.5 1.7
L[bcd]16-[gh] 8 18.4V 19.6V .27 .40 .27 .40 .61  1.1 1.3
L[bcd]18-[gh] 9 20.7V 22.0V .25 .36 .25 .36 .55 1.0 1.2
L[bcd]24-[gh] 12 27.6V 29.4V .19 .28 .19 .28 .42 .77 .92
L[bcd]30-[gh] 15 34.5V 36.7V -- -- -- -- -- .63 .75
L[bcd]36-[gh] 18 41.4V 44.1V -- -- -- -- -- .53 .64
L[bcd]48-[gh] 24 55.2V 58.8V -- -- -- -- -- .40 .50
 
International
Models
100,120,230 or 115/230 Vac 50/60 Hz
Plug-In/Desktop Desktop/IEC
Case Size H F K X Y
Power Code "1" "1" "1" "2" "3" "1" "1"
Enclosure Power Rating for
12V cell voltage
4.0W 6.0W 4.0W 6.0W 9.1W 17W 20W
Model # Cells Float
Charge
Volts
High
Charge
Volts
Charge Current / Amps
L[bcd]06-[gh] 3 6.9V 7.35V .46 .70 .46 .70 1.1 2.0 2.3
L[bcd]08-[gh] 4 9.2V 9.8V .37 .55 .37 .55 .85 1.6 1.9
L[bcd]10-[gh] 5 11.5V 12.25V .32 .49 .32 .49 .74 1.4 1.6
L[bcd]12-[gh] 6 13.8V 14.7V .29 .43 .29 .43 .66 1.2 1.5
L[bcd]16-[gh] 8 18.4V 19.6V .22 .33 .22 .33 .50 .94 1.1
L[bcd]18-[gh] 9 20.7V 22.0V .20 .30 .20 .30 .46 .85 1.0
L[bcd]24-[gh] 12 27.6V 29.4V .15 .23 .15 .23 .35 .65 .77
L[bcd]30-[gh] 15 34.5V 36.7V -- -- -- -- -- .53 .63
L[bcd]36-[gh] 18 41.4V 44.1V -- -- -- -- -- .45 .53
L[bcd]48-[gh] 24 55.2V 58.8V -- -- -- -- -- .35 .40

Case Styles

Standard Input Cords

Standard Output Cords

Theory Of Operation

 

Additional Charger Models

   *P/N System abcdef-gh ex. (L P H N 12-D1)

a - Lead-Acid Charger (L)
b - Mechanical (P=Wall Plug-In, D = Desktop, I = Desktop with IEC 320 Male Inlet)
c - Case Size (H, F, K, X, Y)
d - Input Voltage/Frequency - (N = 120V 60Hz, M = 120V 50/60Hz, E: Euro = 230V 50Hz, U: UK = 230V 50Hz, A: Australian = 240V 50Hz, J: Japan = 100V 50Hz, S = 115/230V 50/60Hz)
ef - Output Voltage Code  ex. (12 = 12 Vdc)
g - Lead-Acid Charger Type - (D = Dual Mode Regulated Current, E = Dual Mode Impedance Limited)
h
- Power Code ex. ("H" Case Power Code 1 = .35 A)

 

For more information or to place an order call (908) 353 5700,
or fax us at (908) 353 1021