MINI POWER FAMILY, 10 - 30 Watts

High Efficiency, Compact Design Switchmode Technology
mini power case samples

Product Links
Related Products
Related Links
UL, cUL, TUV Certified CE marked for European Compliance CEC / DOE EISA 2007 Compliant

    Standard Specifications

  • Universal Input Voltage: 90-264Vac 47-63Hz
  • 75 to 85% efficiency (meets efficiency level 2, 3, 4 or 5 requirements)
  • Output Voltage Tolerance: +/-2.5% Typical, +/-5% Max, from Full Load to No Load.
  • Operating Temperature: 0 - 40C
  • Maximum Output Ripple:
    • 3.3 - 6V: 50mVp-p
    • 6.1 - 22V: 100mVp-p
    • 22.1 - 32V: 150mVp-p
    • 32.1 - 48V: 250mVp-p
  • Designed for Continuous Duty
  • Hold-Up Time : 25mS Minimum @ 120 Vin
  • Short Circuit and Over Load Protection
  • SELV Output
  • MTBF Calculated > 100,000 Hours @ 40C
  • 2 Hour Minimum Loaded Burn-in at 40C Ambient for standard output cord configurations
  • Leakage current compliant to IEC60601-1 Category B and BF
  • 5 Year Warranty
  • See Lower Table for International Energy Efficiency Performance Key

Available Freatures

  • 15W Continuous Output Rating in C Case
  • Expanded Operating Temperatures
  • 400 Hz Input Rating
  • DC Input Rating
  • Additional Noise and/or Surge Protection
  • LED Power On Indicator
  • Output Cord
  • Fixed-in-place Input Cord
  • Wall Plug-in configuration
  • Extended Hold-Up Time
  • Output Cord Sets and Connector Configurations
  • Case Colors, Markings & Logos
  • Output Voltage up to 80VDC
  • 16 Hour Burn-in

Regulatory Compliance

Designed for use with medical, information technology, and general purpose equipment to the following standards: All models are approved to:

  • UL 60601-1 / 60950-1
  • CSA 22.2 #601-1 / #60950-1 *
  • TUV EN 60601-1 / 60950-1
  • CE LVD directive
  • * cUL Mark

EMC All models meet European EMC directive and FCC requirements.
Meet all EMC requirements from EN60601-1-2. Emissions:
Level B requirements of FCC CFR 47 part 15 and CISPR11 (EN55011) and CISPR22 (EN55022), EN61000-6-3 (light industrial) and line harmonic emissions EN61000-3-2.
Immunity: CISPR24 (EN55024), EN61326 and EN61000-3-2.
Certification records available upon project request.

  "C" Case "A" Case
POWER CODE "1" "4" "5"
ENCLOSURE POWER RATING
FOR 12V O/P
10 20 30
Model # VDC amps watts amps watts amps watts
WS[ cd ]33 3.3 1.5 5 3.3 11 5 16
WS[ cd ]39 3.9 1.5 6 3.3 13 5 19
WS[ cd ]45 4.5 1.5 6.8 3.3 15 5 22
WS[ cd ]50 5 1.5 7.5 3.3 17 5 25
WS[ cd ]55 5.5 1.35 7.5 3.1 17 4.5 25
WS[ cd ]60 6 1.25 7.5 2.8 17 4.15 25
WS[ cd ]65 6.5 1.2 7.7 2.6 17 3.8 25
WS[ cd ]70 7 1.15 8.1 2.4 17 3.5 25
WS[ cd ]75 7.5 1.1 8.2 2.3 17 3.3 25
WS[ cd ]80 8 1 8 2.1 17 3.1 25
WS[ cd ]90 9 0.9 8.1 2 18 3 27
WS[ cd ]10 10 0.83 8.3 1.8 18 2.7 27
WS[ cd ]11 11 0.83 9.1 1.7 19 2.5 27
WS[ cd ]12 12 0.83 10 1.7 20 2.5 30
WS[ cd ]13 13 0.77 10 1.5 20 2.3 30
WS[ cd ]14 14 0.71 10 1.4 20 2.15 30
WS[ cd ]15 15 0.67 10 1.3 20 2 30
WS[ cd ]16 16 0.63 10 1.25 20 1.85 30
WS[ cd ]18 18 0.56 10 1.1 20 1.65 30
WS[ cd ]20 20 0.5 10 1 20 1.5 30
WS[ cd ]22 22 0.45 10 0.9 20 1.35 30
WS[ cd ]24 24 0.42 10 0.83 20 1.25 30
WS[ cd ]26 26 0.38 10 0.77 20 1.15 30
WS[ cd ]28 28 0.36 10 0.71 20 1.07 30
WS[ cd ]30 30 0.33 10 0.67 20 1 30
WS[ cd ]32 32 0.31 10 0.62 20 0.94 30
WS[ cd ]36 36 0.28 10 0.56 20 0.83 30
WS[ cd ]40 40 - - 0.5 20 0.75 30
WS[ cd ]44 44 - - 0.45 20 0.68 30
WS[ cd ]48 48 - - 0.42 20 0.63 30
International Energy Efficiency Performance Key to above Table
Color International EPS Efficiency Marking Protocol Category USA/CEC
DOE EISA 2007
Aus/NZ and China Compliance
Green Efficiency Level 5
Blue Efficiency Level 4
Light Blue Efficiency Level 3
- -
Grey Efficiency Level 2 - -
none Efficiency Level 1 - -
Due to a wide variety of custom configuration, we can not mark everything to its exact specs. Please Contact Us if you have special needs.
Energy Performance Regulations
Product Number System, eg:
a b c d ef / ( W S A 4 12 )
a - WideRange ( W )
b - Switchmode ( S )
c - Case Size ( A, C )
d -Power Code ( 1, 4, 5 )
ef - Output Voltage Code ( 12 = 12vdc )

**Add a suffix, "M" for Medical or leave it blank for non-medical.